Elevator Equipment Room Ventilation Requirements
Asme a17 1 the safety code for elevators and escalators requires machine room temperature to be as determined by the elevator manufacturer.
Elevator equipment room ventilation requirements. Most building elevator mechanics and manufacturers maintain elevator machine rooms between 60 f and 80 f with 35 to 60 relative humidity. The environmental systems shall meet the requirements of nfpa standard 110. Elevator machine room will only need ventilation to comply with the code requirement something similar to energy mandatory t 24 in california which requires 15 cfm sq ft. For example in california the ventilation system must keep the temperature below 104 degrees fahrenheit at all times.
The area of vents in the hoistwayor the elevator machine room and the smokehole shall be not less than 31 2percent of the area of the hoistwaynor less than 3 square feet 0 28 m2 for each elevator car whichever is greater. The system is required to be capable of maintaining temperatures within the range established for the elevator equipment 780 cmr 3005 2. Such vents shall comply with the following requirements. The best way to accomodate ventilation for the machine room is to transfer air from adjacent conditioned space.
The air supply and exhaust shall be located so air does not short circuit. Vided to operate an elevator in the event of normal power supply failure the requirements of 2 27 2 1 through 2 27 2 5 shall be complied with. Emergency and standby power systems and meet the combustion air requirements of the equipment. The operating temperature shall be established by the elevator equipment manufacture s specification.
When solid state equipment is used to operate the elevators the elevator equipment room shall be provided with an independent ventilation or air conditioning system to prevent overheating of the electrical equipment. Ventilation rates for storge room 0 12 cfm ft2 0 cfm person electrical equipment rooms 0 06 cfm ft2 0 cfm person and elevator machine rooms 0 12 cfm ft2 0 cfm person are are now included in table 6 1 62 1 2007 whereas 62 1 2004 did not include these spaces in table 6 1. 2 27 2 1 the emergency or standby power system shall be capable of operating the elevator s with rated load see 2 16 8 at least one at a time unless other wise required by the building code. Where standby power is connected to elevators the machine room ventilation or air conditioning is required to be connected to the standby power source 780 cmr 3003 1 4.